ANSI device numbers protection
ANSI device numbers, defined by the IEEE C37.2 standard, provide a system of 99 numeric identifiers to designate protection, control, and switching functions in electric power systems. Their application is universal in single-line diagrams, substation plans, and relay schematics, enabling precise technical communication in the field of electrical engineering.
List of ANSI device numbers (IEEE C37.2)
Section titled “List of ANSI device numbers (IEEE C37.2)”The following table lists 69 device numbers and subnumbers used in electrical system protection, according to ANSI/IEEE C37.2-2008 nomenclature.
| ANSI Number | Designation |
|---|---|
| 1 | Main element (Master Element) |
| 2 | Time delay starting or closing relay |
| 3 | Verification or interlocking relay, complete sequence |
| 4 | Main protection relay |
| 5 | Stopping device – emergency stop switch |
| 6 | Automatic starting switch |
| 7 | Rate of change relay |
| 7F | Rate of change of frequency relay (ROCOF) |
| 8 | Control power disconnecting device |
| 9 | Reversing device |
| 10 | Unit sequence switch |
| 11 | Multifunction device |
| 12 | Overspeed device |
| 13 | Synchronous speed device |
| 14 | Underspeed device |
| 15 | Speed or frequency matching device |
| 16 | Data communications device |
| 17 | Shunt or discharge switch |
| 18 | Acceleration or deceleration device |
| 19 | Starting-to-running transition contactor |
| 20 | Electrically operated valve (solenoid valve) |
| 21 | Distance relay |
| 21G | Ground distance |
| 21P | Phase-to-phase distance |
| 22 | Equalizer circuit breaker |
| 23 | Temperature control device, heater |
| 24 | Volts per hertz relay (V/Hz) |
| 25 | Synchronizing or synchronism check device |
| 26 | Apparatus thermal device, temperature switch |
| 27 | Undervoltage relay |
| 27P | Phase undervoltage |
| 27S | DC undervoltage relay |
| 27TN | Neutral undervoltage by third harmonic |
| 27TN/59N | 100% stator ground fault protection |
| 27X | Auxiliary undervoltage |
| 27 AUX | Auxiliary undervoltage input |
| 27/27X | Bus/line undervoltage |
| 27/50 | Inadvertent energization |
| 28 | Flame detector |
| 29 | Isolating contactor |
| 30 | Annunciator relay |
| 31 | Separate excitation device |
| 32 | Directional power relay |
| 32L | Low forward power |
| 32H | High directional power |
| 32N | Wattmetric zero-sequence directional |
| 32P | Directional power |
| 32R | Reverse power |
| 33 | Position switch |
| 34 | Master sequence device |
| 35 | Brush operating or slip-ring shorting device |
| 36 | Polarity or polarizing voltage device |
| 37 | Undercurrent or underpower relay |
| 37P | Underpower |
| 38 | Bearing protection device / Bearing RTD |
| 39 | Mechanical condition monitor (vibration) |
| 40 | Field relay / loss of excitation |
| 41 | Field circuit breaker |
| 42 | Running circuit breaker |
| 43 | Manual transfer or selector device |
| 44 | Unit sequence starting relay |
| 45 | Atmospheric condition monitor (smoke, fire) |
| 46 | Reverse-phase or stator current unbalance relay |
| 47 | Phase-sequence or voltage unbalance relay |
| 48 | Incomplete sequence relay / locked rotor |
| 49 | Machine or transformer thermal relay / thermal overload |
| 49RTD | RTD-compensated thermal overload |
| 50 | Instantaneous overcurrent relay |
| 50BF | Breaker failure or local backup (LBB) |
| 50DD | Current disturbance detector |
| 50EF | End fault protection |
| 50G | Instantaneous ground overcurrent |
| 50IG | Instantaneous isolated ground overcurrent |
| 50LR | Acceleration time |
| 50N | Instantaneous neutral overcurrent |
| 50NBF | Instantaneous neutral breaker failure |
| 50P | Instantaneous phase overcurrent |
| 50SG | Instantaneous sensitive ground overcurrent |
| 50SP | Split-phase instantaneous current |
| 50Q | Instantaneous negative-sequence overcurrent |
| 50/27 | Inadvertent energization |
| 50/51 | Instantaneous/timed overcurrent relay |
| 50/74 | Current transformer (CT) failure |
| 50/87 | Instantaneous differential |
| 51 | AC time overcurrent relay |
| 51C | Voltage-controlled time overcurrent |
| 51G | Time ground overcurrent |
| 51LR | Locked rotor time overcurrent protection |
| 51N | Time neutral overcurrent |
| 51P | Time phase overcurrent |
| 51R | Locked/stalled rotor |
| 51V | Voltage-restrained time overcurrent |
| 51Q | Time negative-sequence overcurrent |
| 52 | AC circuit breaker |
| 52a | Switch position contact (open when switch is open) |
| 52b | Switch position contact (closed when switch is open) |
| 53 | Exciter or DC generator relay |
| 54 | Turning gear device |
| 55 | Power factor relay |
| 56 | Field application relay |
| 57 | Short-circuit or grounding device |
| 58 | Rectification failure relay |
| 59 | Overvoltage relay |
| 59B | Bank phase overvoltage |
| 59N | Neutral overvoltage |
| 59NU | Neutral voltage unbalance |
| 59P | Phase overvoltage |
| 59X | Auxiliary overvoltage |
| 59Q | Negative-sequence overvoltage |
| 60 | Voltage or current balance relay |
| 60N | Neutral current unbalance |
| 60P | Phase current unbalance |
| 61 | Density switch or sensor |
| 62 | Time delay stopping or opening relay |
| 63 | Pressure detector (pressure switch) |
| 64 | Ground protection relay |
| 64F | Field ground protection |
| 64R | Rotor ground fault |
| 64REF | Restricted earth fault differential |
| 64S | Stator ground fault |
| 64TN | 100% stator ground |
| 65 | Speed governor |
| 66 | Notching device / maximum starts, starts per hour, or time between starts |
| 67 | AC directional overcurrent relay |
| 67G | Directional ground overcurrent |
| 67N | Directional neutral overcurrent |
| 67Ns | Directional ground fault |
| 67P | Directional phase overcurrent |
| 67SG | Directional sensitive ground overcurrent |
| 67Q | Directional negative-sequence overcurrent |
| 68 | Blocking relay / power swing blocking |
| 69 | Permissive control device |
Frequently Asked Questions (FAQ)
Section titled “Frequently Asked Questions (FAQ)”What is an ANSI device number in electrical protection?
Section titled “What is an ANSI device number in electrical protection?”An ANSI device number is a standardized numeric code that identifies a protection, control, or supervision function in electrical equipment, according to the IEEE C37.2 standard. Each number represents a specific operation, for example, 50 corresponds to instantaneous overcurrent and 51 to time overcurrent.
What is the difference between number 50 and number 51?
Section titled “What is the difference between number 50 and number 51?”Number 50 designates an instantaneous overcurrent protection, which operates without intentional delay when the current exceeds the set threshold. Number 51 indicates a time overcurrent protection, whose trip time is inversely proportional to the current magnitude (inverse time curve) or defined by a fixed delay.
Can multiple ANSI numbers be combined in the same relay?
Section titled “Can multiple ANSI numbers be combined in the same relay?”Yes, it is a common practice in modern numerical relays (IEDs). A single device can implement multiple functions indicated by numbers separated by a slash, such as 50/51 (instantaneous and time overcurrent) or 67/67N (directional phase and neutral), which is reflected in single-line diagrams.
Which ANSI number protects against ground faults in the stator of a generator?
Section titled “Which ANSI number protects against ground faults in the stator of a generator?”The most commonly used functions are 64S (stator ground fault), 64TN (100% stator protection), and 27TN/59N, which monitors third harmonic voltage and residual voltage to detect faults along the entire winding length.
How is a number like 50/87 interpreted in a protection scheme?
Section titled “How is a number like 50/87 interpreted in a protection scheme?”The notation 50/87 combines the instantaneous overcurrent function (50) with instantaneous differential protection (87). It is generally used for schemes where an instantaneous overcurrent element backs up the main differential protection, ensuring fast tripping for internal faults.
Where is number 87 typically applied?
Section titled “Where is number 87 typically applied?”Number 87 corresponds to differential protection. It is applied in power transformers (87T), generators (87G), buses (87B), and transmission lines (87L), comparing currents entering and leaving the protected zone to detect internal faults with high sensitivity.
References
Section titled “References”- engineeringtoolbox.com: https://www.engineeringtoolbox.com/isa-intrumentation-codes-d_415.html