Skip to content

ANSI device numbers protection

ANSI device numbers, defined by the IEEE C37.2 standard, provide a system of 99 numeric identifiers to designate protection, control, and switching functions in electric power systems. Their application is universal in single-line diagrams, substation plans, and relay schematics, enabling precise technical communication in the field of electrical engineering.

The following table lists 69 device numbers and subnumbers used in electrical system protection, according to ANSI/IEEE C37.2-2008 nomenclature.

ANSI Number Designation
1 Main element (Master Element)
2 Time delay starting or closing relay
3 Verification or interlocking relay, complete sequence
4 Main protection relay
5 Stopping device – emergency stop switch
6 Automatic starting switch
7 Rate of change relay
7F Rate of change of frequency relay (ROCOF)
8 Control power disconnecting device
9 Reversing device
10 Unit sequence switch
11 Multifunction device
12 Overspeed device
13 Synchronous speed device
14 Underspeed device
15 Speed or frequency matching device
16 Data communications device
17 Shunt or discharge switch
18 Acceleration or deceleration device
19 Starting-to-running transition contactor
20 Electrically operated valve (solenoid valve)
21 Distance relay
21G Ground distance
21P Phase-to-phase distance
22 Equalizer circuit breaker
23 Temperature control device, heater
24 Volts per hertz relay (V/Hz)
25 Synchronizing or synchronism check device
26 Apparatus thermal device, temperature switch
27 Undervoltage relay
27P Phase undervoltage
27S DC undervoltage relay
27TN Neutral undervoltage by third harmonic
27TN/59N 100% stator ground fault protection
27X Auxiliary undervoltage
27 AUX Auxiliary undervoltage input
27/27X Bus/line undervoltage
27/50 Inadvertent energization
28 Flame detector
29 Isolating contactor
30 Annunciator relay
31 Separate excitation device
32 Directional power relay
32L Low forward power
32H High directional power
32N Wattmetric zero-sequence directional
32P Directional power
32R Reverse power
33 Position switch
34 Master sequence device
35 Brush operating or slip-ring shorting device
36 Polarity or polarizing voltage device
37 Undercurrent or underpower relay
37P Underpower
38 Bearing protection device / Bearing RTD
39 Mechanical condition monitor (vibration)
40 Field relay / loss of excitation
41 Field circuit breaker
42 Running circuit breaker
43 Manual transfer or selector device
44 Unit sequence starting relay
45 Atmospheric condition monitor (smoke, fire)
46 Reverse-phase or stator current unbalance relay
47 Phase-sequence or voltage unbalance relay
48 Incomplete sequence relay / locked rotor
49 Machine or transformer thermal relay / thermal overload
49RTD RTD-compensated thermal overload
50 Instantaneous overcurrent relay
50BF Breaker failure or local backup (LBB)
50DD Current disturbance detector
50EF End fault protection
50G Instantaneous ground overcurrent
50IG Instantaneous isolated ground overcurrent
50LR Acceleration time
50N Instantaneous neutral overcurrent
50NBF Instantaneous neutral breaker failure
50P Instantaneous phase overcurrent
50SG Instantaneous sensitive ground overcurrent
50SP Split-phase instantaneous current
50Q Instantaneous negative-sequence overcurrent
50/27 Inadvertent energization
50/51 Instantaneous/timed overcurrent relay
50/74 Current transformer (CT) failure
50/87 Instantaneous differential
51 AC time overcurrent relay
51C Voltage-controlled time overcurrent
51G Time ground overcurrent
51LR Locked rotor time overcurrent protection
51N Time neutral overcurrent
51P Time phase overcurrent
51R Locked/stalled rotor
51V Voltage-restrained time overcurrent
51Q Time negative-sequence overcurrent
52 AC circuit breaker
52a Switch position contact (open when switch is open)
52b Switch position contact (closed when switch is open)
53 Exciter or DC generator relay
54 Turning gear device
55 Power factor relay
56 Field application relay
57 Short-circuit or grounding device
58 Rectification failure relay
59 Overvoltage relay
59B Bank phase overvoltage
59N Neutral overvoltage
59NU Neutral voltage unbalance
59P Phase overvoltage
59X Auxiliary overvoltage
59Q Negative-sequence overvoltage
60 Voltage or current balance relay
60N Neutral current unbalance
60P Phase current unbalance
61 Density switch or sensor
62 Time delay stopping or opening relay
63 Pressure detector (pressure switch)
64 Ground protection relay
64F Field ground protection
64R Rotor ground fault
64REF Restricted earth fault differential
64S Stator ground fault
64TN 100% stator ground
65 Speed governor
66 Notching device / maximum starts, starts per hour, or time between starts
67 AC directional overcurrent relay
67G Directional ground overcurrent
67N Directional neutral overcurrent
67Ns Directional ground fault
67P Directional phase overcurrent
67SG Directional sensitive ground overcurrent
67Q Directional negative-sequence overcurrent
68 Blocking relay / power swing blocking
69 Permissive control device

What is an ANSI device number in electrical protection?

Section titled “What is an ANSI device number in electrical protection?”

An ANSI device number is a standardized numeric code that identifies a protection, control, or supervision function in electrical equipment, according to the IEEE C37.2 standard. Each number represents a specific operation, for example, 50 corresponds to instantaneous overcurrent and 51 to time overcurrent.

What is the difference between number 50 and number 51?

Section titled “What is the difference between number 50 and number 51?”

Number 50 designates an instantaneous overcurrent protection, which operates without intentional delay when the current exceeds the set threshold. Number 51 indicates a time overcurrent protection, whose trip time is inversely proportional to the current magnitude (inverse time curve) or defined by a fixed delay.

Can multiple ANSI numbers be combined in the same relay?

Section titled “Can multiple ANSI numbers be combined in the same relay?”

Yes, it is a common practice in modern numerical relays (IEDs). A single device can implement multiple functions indicated by numbers separated by a slash, such as 50/51 (instantaneous and time overcurrent) or 67/67N (directional phase and neutral), which is reflected in single-line diagrams.

Which ANSI number protects against ground faults in the stator of a generator?

Section titled “Which ANSI number protects against ground faults in the stator of a generator?”

The most commonly used functions are 64S (stator ground fault), 64TN (100% stator protection), and 27TN/59N, which monitors third harmonic voltage and residual voltage to detect faults along the entire winding length.

How is a number like 50/87 interpreted in a protection scheme?

Section titled “How is a number like 50/87 interpreted in a protection scheme?”

The notation 50/87 combines the instantaneous overcurrent function (50) with instantaneous differential protection (87). It is generally used for schemes where an instantaneous overcurrent element backs up the main differential protection, ensuring fast tripping for internal faults.

Number 87 corresponds to differential protection. It is applied in power transformers (87T), generators (87G), buses (87B), and transmission lines (87L), comparing currents entering and leaving the protected zone to detect internal faults with high sensitivity.